ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

Transformer trips ,After recommissioning of Differential relay in YNd1 Transformer Protection panel. What are the probable reason ?

user-image
تم إضافة السؤال من قبل Himadri Roy , MANAGER ELECTRICAL , STEAG ENERGY SERVICES
تاريخ النشر: 2018/01/07
Aneesh Shandilya
من قبل Aneesh Shandilya , Manager/ Lead Electrical , Orpic

The probable reasons are:

1) Real Fault in transformer

2) Wrong connections of CTs

3) Wrong configuration of the relay

You need to carry out following:

1) Test the transformer for its healthiness

2) Carry out stability test for diffenrential protection circuit to investigate the discrepancy, which is leading to trip.

Shankar Kumar
من قبل Shankar Kumar , Senior Testing and commissioning Engineer , ENGSOL

INRUSH CURRENT AND DIFFERENTIAL PROTECTION CT SATURATION AT HV SIDE

Saad Qamar
من قبل Saad Qamar , Electrical Technician , SAKA

3 Main causes

1. Inrush currents

2. Overexcitation conditions

3.current transformer saturation

 

alok ranjan
من قبل alok ranjan , Electrical & Instrumentation Engineer , SHYAM STEEL INDUSTRIES LTD

check for the derived earth fault setting & measured earth faoult with there time setting.

selva raj
من قبل selva raj , M/s. Imanco Company

wrong configuration of the Relay

Vonani Given Makamu
من قبل Vonani Given Makamu , Senior Electrical Technician , SASOL LTD

Real fault in transformer

Wrong connection of CTs.

Wrong configuration of the relay.

 

المزيد من الأسئلة المماثلة

هل تحتاج لمساعدة في كتابة سيرة ذاتية تحتوي على الكلمات الدلالية التي يبحث عنها أصحاب العمل؟