Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Transformer trips ,After recommissioning of Differential relay in YNd1 Transformer Protection panel. What are the probable reason ?

user-image
Question added by Himadri Roy , MANAGER ELECTRICAL , STEAG ENERGY SERVICES
Date Posted: 2018/01/07
Aneesh Shandilya
by Aneesh Shandilya , Manager/ Lead Electrical , Orpic

The probable reasons are:

1) Real Fault in transformer

2) Wrong connections of CTs

3) Wrong configuration of the relay

You need to carry out following:

1) Test the transformer for its healthiness

2) Carry out stability test for diffenrential protection circuit to investigate the discrepancy, which is leading to trip.

Shankar Kumar
by Shankar Kumar , Senior Testing and commissioning Engineer , ENGSOL

INRUSH CURRENT AND DIFFERENTIAL PROTECTION CT SATURATION AT HV SIDE

Saad Qamar
by Saad Qamar , Electrical Technician , SAKA

3 Main causes

1. Inrush currents

2. Overexcitation conditions

3.current transformer saturation

 

alok ranjan
by alok ranjan , Electrical & Instrumentation Engineer , SHYAM STEEL INDUSTRIES LTD

check for the derived earth fault setting & measured earth faoult with there time setting.

selva raj
by selva raj , M/s. Imanco Company

wrong configuration of the Relay

Vonani Given Makamu
by Vonani Given Makamu , Senior Electrical Technician , SASOL LTD

Real fault in transformer

Wrong connection of CTs.

Wrong configuration of the relay.

 

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.