Communiquez avec les autres et partagez vos connaissances professionnelles

Inscrivez-vous ou connectez-vous pour rejoindre votre communauté professionnelle.

Suivre

Can a control valve be mounted with actuator in horizontal position ?

user-image
Question ajoutée par MOHAMMAD IMTIYAZ UDDIN , Instrumentation Engineer , BOC
Date de publication: 2017/03/10
Abdeldjalil ACHOUR
par Abdeldjalil ACHOUR , Senior Technician , SONATRACH

I think that is better for some types of cotrol valves to be installed verticaly, sliding stem for example, however other types can be mounted in horizontal position like rotary valves .

Selvam Palaniappan
par Selvam Palaniappan , Senior Application Engineer , Emerson Automation Solutions

Yes, we can mount the control valve in horizontal position. For larger sizes we need to provide some balancing columns.

MOHAMMAD IMTIYAZ UDDIN
par MOHAMMAD IMTIYAZ UDDIN , Instrumentation Engineer , BOC

Yes. Control valves can work in any orientation,however the preferred installation is with actuator in vertical position.This will prevent side loading of the internal components,the valve will have a much longer service life and maintenance easier.However a special attention must be paid to the following aspects whenever the horizontal installation is provided:

  • steam jacketing,if provided ,must grant a good condensate drain;this means that steam jacketing outlet connection shall be in the lowest possible position
  • accessories such as filter airset,solenoid valve etc. must be installed in upright position

The requst of installation with actuator in horizontal position must always and clearly be indicated to the manufacturer of the control valve.

Valves on Cryogenic service(-100 degree celsius & below) must not be installed with actuator in horizontal position.

Shams Ul  islam
par Shams Ul islam , Lead Engineer electrical , DESCON Engineering

control valve always install vertically because of upper disc pressure 

Rodney Lawrence Naidoo
par Rodney Lawrence Naidoo , Process Controller , Air Liquide Southern Africa

That would depend on the position of the control valve. It would, to an extent depend on the application.