Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Can a control valve be mounted with actuator in horizontal position ?

user-image
Question added by MOHAMMAD IMTIYAZ UDDIN , Instrumentation Engineer , BOC
Date Posted: 2017/03/10
Abdeldjalil ACHOUR
by Abdeldjalil ACHOUR , Senior Technician , SONATRACH

I think that is better for some types of cotrol valves to be installed verticaly, sliding stem for example, however other types can be mounted in horizontal position like rotary valves .

Selvam Palaniappan
by Selvam Palaniappan , Senior Application Engineer , Emerson Automation Solutions

Yes, we can mount the control valve in horizontal position. For larger sizes we need to provide some balancing columns.

MOHAMMAD IMTIYAZ UDDIN
by MOHAMMAD IMTIYAZ UDDIN , Instrumentation Engineer , BOC

Yes. Control valves can work in any orientation,however the preferred installation is with actuator in vertical position.This will prevent side loading of the internal components,the valve will have a much longer service life and maintenance easier.However a special attention must be paid to the following aspects whenever the horizontal installation is provided:

  • steam jacketing,if provided ,must grant a good condensate drain;this means that steam jacketing outlet connection shall be in the lowest possible position
  • accessories such as filter airset,solenoid valve etc. must be installed in upright position

The requst of installation with actuator in horizontal position must always and clearly be indicated to the manufacturer of the control valve.

Valves on Cryogenic service(-100 degree celsius & below) must not be installed with actuator in horizontal position.

Shams Ul  islam
by Shams Ul islam , Lead Engineer electrical , DESCON Engineering

control valve always install vertically because of upper disc pressure 

Rodney Lawrence Naidoo
by Rodney Lawrence Naidoo , Process Controller , Air Liquide Southern Africa

That would depend on the position of the control valve. It would, to an extent depend on the application.

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.