What is the significance of knee voltage for protection CT? Please explain with an example?

user-image
Question ajoutée par manzoor ummar , Electrical Engineer , Tata Consulting Engineers
Date de publication: 2016/08/06
Aneesh Shandilya
par Aneesh Shandilya , Manager/ Lead Electrical , Orpic

Knee Point Voltage of Current Transformer is the significance of saturation level of a CT core mainly used for protection purposes. The sinusoidal voltage of rated frequency applied to the secondary terminals of current transformer, with other winding being open circuited, which when increased by 10% cause the exiting current to increase 50%.

In differential and restricted earth fault (REF) protection scheme, accuracy class and ALF of the CT may not ensure the reliability of the operation. It is desired that, differential and REF relays should not be operated when fault occurs outside the protected transformer. When any fault occurs outside the differential protection zone, the faulty current flows through the CTs of both sides of electrical power transformer. The both LV and HV CTs have magnetizing characteristics. Beyond the knee point, for slight increase in secondary emf a large increasing in excitation current is required. So after this knee point excitation current of both current transformers will be extremely high, which may cause mismatch between secondary current of LV & HV current transformers. This phenomena may cause unexpected tripping of power transformer. So the magnetizing characteristics of both LV & HV sides CTs, should be same that means they have same knee point voltage Vk as well as same excitation current Ieat Vk/2. It can be again said that, if both knee point voltage of current transformer and magnetizing characteristic of CTs of both sides of power transformer differ, there must be a mismatch in high excitation currents of the CTs during fault which ultimately causes the unbalancing between secondary current of both groups of CTs and transformer trips. So for choosing CT for differential protection of transformer, one should consider current transformer PS class rather its convectional protection class. PS stands for protection special which is defined by knee point voltage of current transformer Vk and excitation current Ie at Vk/2.

Muhammad Qasim
par Muhammad Qasim , Senior Electrical Engineer , Energy Associates (SMC Ptv.) Ltd.

Dear Manzoor Umar! Its a an important question but answer and example needs a lot of explanation that is difficult for me to write all here. However here i am sharing with you an important link that will help you in understanding the answer. www.electrical4u.com/knee-point-voltage-of-current-transformer-ps-class/