Normally pin support is used for steel super-structure to concrete sub-structure what if fixed support is used there?

user-image
Question ajoutée par Muhammad Sohail , Principal Engineer , BUILDCON Consulting Engineers
Date de publication: 2015/12/06
Alpeshkumar Renpara
par Alpeshkumar Renpara , Junior Project Engineer , Setu Infratech

Moment transfers to concrete base structure

Requires strong concrete element to resist moment induced cracks

Expensive

Time consuming

Ernest Christian Nanola
par Ernest Christian Nanola , Senior Structural Engineer , Makati Development Corporation

I already tried to make a fixed supported steel on concrete structure and the following are the results:

1. the steel is section is lighter, however

2. the number of bolts are greater

3. the baseplate is thicker

4. the analysis of the concrete itself always fails in terms of bolt pull out, edge distance of the bolts must be great(minimum edge distance will not work all the time) even with densed reinforcement around the bolts.

 

 