Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

How can a D.P. transmitter be calibrated?

user-image
Question added by Wajid Imran Abbasi , Instrument Engineer , OGDCL
Date Posted: 2014/06/14
Bilal Ahmed
by Bilal Ahmed , Instrument Engineer In Training , OGDCL

1.     D.P. transmitter can be calibrated using following  steps:

1. Adjust zero of Xmtrs.2. Perform static pressure test: Give equal pressure on both sides of transmitter. Zero should not shift either side. If the zero shifts then carry out static alignment. 3. Perform vacuum test: Apply equal vacuum to both the sides. Zero should not shift. 4. Calibration procedure: Give20 psi air supply to the transmitter and vent L.P. side to atmosphere. Connect output of the instrument to the standard test gauge. Adjust zero. Apply required pressure to the high pressure side and adjust the span. Adjust zero gain if necessary.

mohamed eliwa
by mohamed eliwa , instrument and control engineer , egyptian maintenance company 'emc'

Zero calibration make low and high to atmosphere zero differential  press zero button or tune button according transmitter then to calibrate span inject pressure from pump to set point then press span or tune the button ensure20ma 

make a2nd trial to ensure linear output 

mahir abd it abd eed al hassan
by mahir abd it abd eed al hassan , QC Site engineer , Restrata company

yes correct

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.