Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Can we connect FHC in Auto Wet Sprinkler close loop dia 100mm after the Zone CONTROL VALVE?

user-image
Question added by Candido Cabral
Date Posted: 2016/06/28
Arul kumaran panneerselvam
by Arul kumaran panneerselvam , Mechanical Engineer (Plumbing & Fire Fighting) , TRAGS Electrical & Air-Conditioning CO.

We cannot connect the FHC line intomm dia auto wet sprinkler close loop after Zone control valve. It should be before the Zone control valve .

ansari azhar
by ansari azhar , designer engineer , Saudi Factory For Fire Equipments (SFFECO)

NO ITS BETTER TO TAKE A SEPRATE LINE BEFORE ZONE CONTROLE VALAVE

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.