Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Are we obliged to make the "Return Bend" before any sprinkler? What is the situation in which we can cancel it?

user-image
Question added by Zaid Al Shurafa , Mechanical Project Engineer , Amana Contracting And Steel Buildings - DUBOX
Date Posted: 2016/04/26
harish alam
by harish alam , Mechanical Engineer , Seder Group

Hi,

 

Return bends are mandatory to provide to avoid accumulation of sediments in the drop nipple except in these below cases:

  • Deluge sprinkler system
  • Dry sprinkler system
  • And the sprinkler with K value 11.2 or more.

mahmoud elshinnawi
by mahmoud elshinnawi , Lead Mechanical Engineer – Site Based , ASAS Electromechanical contractors

The obligation depends on the local authority, or the standard followed in the region. If the system is a dry type, no need for the return bend.

Satej Jaokar
by Satej Jaokar , Mechanical QC Enginner , Saudi Oger Ltd

Yes, Not required in deluge system & dry pendant sprinlers. Will be given consideration if using potable water, depends on approval authority.

jay vargas
by jay vargas , Plumber , 2014 Saudi Archirodon Ltd

yes. because the purpose of return bend is to stop the smells to come back.it is nessesary to use it.

Mohammed Shebl
by Mohammed Shebl , Contract and Commercial Manager , China Railway Construction co.ltd

according code , if we use pure water from tank we will not need to put return bend , because  the purpose of a return bend is to prevent the accumulation of sediment in the pipe drop to a fire sprinkler 

Zaid Al Shurafa
by Zaid Al Shurafa , Mechanical Project Engineer , Amana Contracting And Steel Buildings - DUBOX

I have checked the NFPA 13 code , and I found that we can ignore it if we have 11 K-factor or above for sprinklers , otherwise we must use return bend .But is saudi arabia I saw many project they ignore it , Although they use sprinklers with 5.6 K-factor !!

mohammed ateeq
by mohammed ateeq , Electrical draughtsman , Electrical draughtsman

as per consultant request intragroup

Firozalam Siddiqui
by Firozalam Siddiqui , SENIOR ELECTRICAL ENGINEER , DAR AL RIYADH

Yes, considering site condition, it can be provided and acceptable. In case it can be avoid or ignored as per K factor's value.

gouse peer syed
by gouse peer syed , Site & Maintenance Engineer , Arab air conditioning & refrigeration.co

No problem, we can take return bend before the sprinkler. but need to follow the design specification as per site requirement. we need to check flow rate & pressure.

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.