What will be the Out going cable size for 40A TP MCCB ?

user-image
Question added by Arsalan Haider , Electrical Engineer/Quality Control , Gulf Sail Specialized Engineering Company
Date Posted: 2015/08/29
Sattar Abdulkarim  Mohamed
by Sattar Abdulkarim Mohamed , Country Sales Director , Ideal Technical Solutions

Before limitation the cross section of the ongoing cable of 40A MCCB  need to know the following :

1- Load level connected

2- System Voltage

3-Cable length

4- Type of the Conductor Copper or Aluminum  with PVC Insulation

MCCB/ Molded Case Circuit Breaker is normally used for the voltage 3-phase 380Volt  and 220Volt line to Neutral.  MCCB has  a thremal release for the over current protection & Magnetic release for the Short Circuit Protection. Convenient Cross Section of the cable for 40A MCCB is 4-6 MM Square.

Farrag  Fisal
by Farrag Fisal , Electrical Engineer , Sayed Hamid Behbehani & Sons ( SHBC)

10mm Sq in Copper conductor

16mm sq in Aluminum conductor 

siddique ur Rehman
by siddique ur Rehman , Assistant Electrical Engineer , Kashif Aslam & Associates Pvt. Limited

10mm Sq in Copper conductor

16mm sq in Aluminum cxonductor 

 

If Length is less then 50 meter

Faheem Haider
by Faheem Haider , Electrical Inspector , Great Attractions

16mm sq. copper conductor.

Muhammad Moneeb Akhtar
by Muhammad Moneeb Akhtar , Freelance , UPWORK

Although, there are plenty of requirements before deciding a 'final conductor size' but i would like to share with you something simple i.e rule of thumb.or a 'three phase system' divide the  circuit breaker size with '4' and use the 'next standard cable size' for installation. In this case "40/4=10". So i would recommend you to choose 10 mm24/Core Cu. conductor cable if distance is short upto 100-150 feet otherwise use next bigger size (16 mm2)

Yousef Asaad Sofan
by Yousef Asaad Sofan , Electrical Design Engineer/Revit specialist , Architectural Design House Company A.D.H.C دار التصاميم المعماريه

It's depends in  many factors 

1- type of load 

2- distance between DB & and the load 

3- type of conductor

4- type of installation

5- type of isolation

6-future expansion 

 

Stanley Mutandwa
by Stanley Mutandwa , Power Technician , Tendo Electronics & Power Engineering

6 square millimeter is the correct size

 

mahmood mahmood
by mahmood mahmood , electrical engineer , Ministry of Electricity

cross section area of the cable

(10) mm2

 

 

Elsayed Magdy Elsayed Mohamed Mohamed
by Elsayed Magdy Elsayed Mohamed Mohamed , Security,……………

 % Cable with size less than 10mm2 with calculate suitable   VD

Muhammad  Rizwan
by Muhammad Rizwan , Senior Electrical Technician , Lotte Kolson pvt limitd

10mm sq of copper conductor

SAHAD KOYANGODAN
by SAHAD KOYANGODAN , MEP Electrical Engineer , Consoldiated Proserve Electromechanical Works LLC.

It is not a unique answer question. The answer depends on type of load (critical loads need more protectoin). Moreover in UAE it is generally 10 sq.mm cable for a 40A, TP, MCCB.