How to calculate TMBH & SMBH for FAHU? Example we have calculated fresh Air supply of 3125 L/s or 6650 cfm what will be TMBH and SMBH for FAHU

user-image
Question added by Mohammed Asim
Date Posted: 2015/08/26
Osama Taghlebi
by Osama Taghlebi , MEP , Private

 

SMBH =1.085 x (CFM/1000) x (∆T air)

 

TMBH =4.5 x (CFM/1000) x (∆h air)

 