Hi All In CHW system, EWT/LWT CHW temp for AHU are 5&12 degC Room setpoint shall be 22 degC & return = 23 degC Total supply air, say 4000 L/s?

In such case what's ideal supply air temp & how is it calculated considering heat transfer between CHW & supply air?  What parameters can be controlled to vary supply air temp & what's the range of supply air temp that can be achieved for above scenario?

user-image
Question added by Mohsin Khan , Mechanical Design Engineer , ChapmanBDSP
Date Posted: 2019/10/26
Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

Normally the supply air temperature is kep 14-15 Deg C.

The formula for sensible load is

Sensible heat = (mass of the body) * (specific heat capacity) * (change of the temperature)

 

You can derive what ever the value you need from this equation

Hope this will be fine

 