Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

How can you estimate evaporation from cooling tower?

user-image
Question added by dana tutunji , Architect , Helou Trading Co
Date Posted: 2013/06/27

Given the volume of the bassin is known, close make up valve and record the level dropped per hour.
Convert to volume dropped per hour and this will be the volume of water evaporating per hour.

ishtiaq hussain zaidi
by ishtiaq hussain zaidi , Executive officer-II A/C maintenance , feroze 1888 mills ltd

i think, simply installed a water flow meter in fresh water make-up line of c/t and note the hourly reading. the difference b/w two readings, will be quantity of evaporated water.

am i right?

Prabhakar Naik
by Prabhakar Naik , Engineering Manager , VASTU & ENGG CONSULTANCY DMCC, JLT

Not necessarily.
What happens to the blow down and drift losses then? U will end up measuring total loss of water by the above method unless you deduct the other two components!

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.