ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

What are the problems that we might face, if we run a 2M Watt GenSet In no load mode for 6 hours daily?

The GenSet will be hybrid with  2M Watt Solar Arrays, the Gen set will be needed when the sun irradiation is not enough (cloudy hours/days) only.

user-image
تم إضافة السؤال من قبل Hesham Al-Arashi , independent electrical engineer and registered electrical engineering consultant , Many Organizations
تاريخ النشر: 2016/12/14
subhash UPDA REGISTERED
من قبل subhash UPDA REGISTERED , TESTING AND COMMISSIONING ENGINEER , NEMCCO

It will not get serious harm for generator. what happen if unloaded are explained as follows

stator will not create counter magnet force (since current becomes zero)

rotor will starts to increase its speed.         ( since no counter force coming from stator)

it will increase some speed than normal.

diesel engine have system of constant speed controller it senses the rpm and send control to fuel throttle to generate less mechanical power.

and system will go in idle/ stand by mode.

mohamad Bakri
من قبل mohamad Bakri , Senior project Manager , Eiffel engineering

Hi

 technically no problem  , but you loose fuel for nothing..

المزيد من الأسئلة المماثلة

هل تحتاج لمساعدة في كتابة سيرة ذاتية تحتوي على الكلمات الدلالية التي يبحث عنها أصحاب العمل؟