ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

Can we use control valve without positioner ?

user-image
تم إضافة السؤال من قبل Faseem Abdulla Kattil Veedu , Lead Instrumentation Engineer/Procurement Engineer , Sinopec Branch Of International Petroleum Coorporation
تاريخ النشر: 2016/02/28
shahab din
من قبل shahab din , Operation and Maintenance Electrical Engineer , EG&G Middle East

yes , we can control valve with out positioner as positioner has to do nothiing with valve control it only tells us the position of valve. when i used to work on well head projects i have come across this experience, we used positioner to know the about the position of valve from upstream to down stream. and from that value of positioner you can control the through pneumatic way or manual, in short positioner only help you to know the position of valve

othman fawzy
من قبل othman fawzy , Instrumentation and Control Engineer , cairo electericity production company (CEPC)

the positioner is a main part of the control valve to perform the control function

Islam abd Elrhman Hussein
من قبل Islam abd Elrhman Hussein , Instrumentation Engineer PMT , WOOD PLC

Control valve can not be without positioner. The purpose of the positioner is to control the control valve stroke so as to keep the valve in desired position. The positioner receives signal from the controller, and send the boosted signal to the actuator to reach the desired position as and when the valve reaches the desired position the positioner cuts the boosted signal to the actuator and keeps the position.the following are the application to use valve with positinor:

1-split range control action.2-reverse acting actuator.3-valve size large than 3"(8cm)4-actuator power requirment in excess of controller out put.5-valve design inhrent of flow chractristics change.6-line pressure above 20bar or delta pressure more than 14 bar7-quick response actuator.8-elminated the hystersis.

but in certain cases  when we the positioner fail and we haven't spare we can use I/P converter tranceducer, solenoid valve or air regulator  to open the control valve meanwhile to optain the positioner .

 

Roland Felix
من قبل Roland Felix , Supervisor Electrical & Instrumentation , GCC-Gulf Consolidated Contractors Company LTD

Ofcourse we use the control valve without positioner

 

Shilpa Joshi
من قبل Shilpa Joshi , Instrumentation and Control Engineer , Thermax

Yes A control valve can be used without a positioner (eg. Manually operated control valves) but if the valve is pneumatically actuated a E to P converter is must & without positioner there will not be any valve position feedback available, the valve operation may not be accurate & tight shut off for higher valve sizes will not be available.

Ashish Dixit
من قبل Ashish Dixit , JUNIOR ENGINEER , ESSJAY ERICSSON PRIVATE LIMITED

Yes , we can  use control  valve without  positioner . Because positioner  is used for quick operation of control valve. 

Adnan Ahmad
من قبل Adnan Ahmad , Senior Electrical Engineer , Engro Polymer and Chemicals ( Petrochemical Plant)

The Positioner is the integral part of control valve. Through positioner the position of control valve is controlled. In case of mechnical valves or Regulators the purpose can be meet without the postioner.

Muhammad Yousuf
من قبل Muhammad Yousuf , QA/QC Instrumentation Inspector / Engineer , Tunisian Saudi for Projects Company Ltd. (EPPM)

Control valve can not be without positioner

المزيد من الأسئلة المماثلة

هل تحتاج لمساعدة في كتابة سيرة ذاتية تحتوي على الكلمات الدلالية التي يبحث عنها أصحاب العمل؟