Communiquez avec les autres et partagez vos connaissances professionnelles

Inscrivez-vous ou connectez-vous pour rejoindre votre communauté professionnelle.

Suivre

How high voltage regulation transformer can be used to reduce fault currents in a circuit?

user-image
Question ajoutée par Muhammad Usman , Assistant Manager Operations , Lahore Electric Supply Company
Date de publication: 2016/08/17
Mohamed Rabia Elhadad
par Mohamed Rabia Elhadad , Electrical Maintenance Engineer , YES-PAK

it can prevent the zero sequence current

Muhammad Qasim
par Muhammad Qasim , Senior Electrical Engineer , Energy Associates (SMC Ptv.) Ltd.

Let me clear on thing that as per my understanging, question is not narrated properly. Infect its not transformer that helps in limiting the fault current. As transformer is always there and contributes a specific percent impedence in the system. However high voltage transformer those are equipped with onload tap changer (voltage regulation) has an edge in limiting the fault current. As this onload tap controbute additional impedence that can either be resistive or reactive and hence limit the fault current. So infect question should be that, How can an onload tap changer helps in limiting the faulty current in an HV Transformer. Regards

High impedance transformer can reduce fault currents, or inserting current limiting reactor in secondary side of transformer can reduce fault currents depending on criteria of acceptable levels of short circuit and voltage regulation for a given application

manzoor ummar
par manzoor ummar , Electrical Engineer , Tata Consulting Engineers

The fault current in a system will be limited by the impedance in the system. When you include transformer in the circuit, its reactance will reduce the fault current.