Communiquez avec les autres et partagez vos connaissances professionnelles

Inscrivez-vous ou connectez-vous pour rejoindre votre communauté professionnelle.

Suivre

For chilled water system, what is the formula or the relation of TR and GPM? rule of thumb is 2.4 for each 1 TR .

user-image
Question ajoutée par Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company
Date de publication: 2015/06/29
pradeep KUZHIYANJAL
par pradeep KUZHIYANJAL , Senior Project Engineer , LAITH ELECTROMECHANICAL WORKS LLC, ABU DHABI,U.A.E

Tons = gpm x delta T / 24

delta T - temperature diffrence chilled water

sameh shahat
par sameh shahat , Site Engineer , PROJECT BUILD CO.

1- Chiller Ton = (GPMx∆T (Delta Temp)) /24    

2- cooling Tower Ton= ( GPMx∆T (Delta Temp)) /30

        

 

             

MOHAMMED SIDDIQ  ALI KHAN
par MOHAMMED SIDDIQ ALI KHAN , Mechanical Bim Modeler cum MEP Draughtsman , voltas ltd doha qatar & al yamama saudi arabia

4.4 us gpm = 1 m3/hr

Q = m Cp Temp diff

m/v = density

m=denisity x vol

Ehab Tuffaha
par Ehab Tuffaha , MEP Manager , mep enterprises

Total Tonnage of chillers =( 500 x GPM X Delta T (F) )  / 12000

TTotal Tonnage of cooling towers = ( 500 x GPM X Delta T (F) )  / 15000

In this application, the cooling tower must handle a building load of 12,000 BTUH per ton plus the compressor heat of about 3,000 BTUH/ton.1 Design ∆T (Design Temperature Drop) This is conservative in light of today’s chiller efficiencies, which often consume less than 3,000 BTUH/ton.

 

Gella Bharat
par Gella Bharat , HVAC Engineer , Load Calculation

4.4 us gpm = 1 m3/hr

Q = m Cp Temp diff

m/v = density

m=denisity x vol

based on the temperature diff of chilled water flow is established

 

Babak Kaberi
par Babak Kaberi , Project Coordinator for Engineering Affairs , IOID

Dear Sharif.

1- For evaporator: the equation for water chiller is Q=500GPM (T2-T1) Where Q is in [Btu/hr] and T is in [F]. Converting Btu/hr to TR  (dividing by12000) and considering10 degrees Fahrenheit for temperature difference (water inlet-water outlet), we reach the following formula:

TR=0.42GPM

2- For condenser in water cooled condensers: Consider3 GPM for one TR.

Please note that it may vary depends on temperature difference in your system.

Regards 

  

Muhammad Ahsan
par Muhammad Ahsan , Taxtail mill , Compressor & chiller

Compressor & chiller plant incharge

AHMED HUSSEIN
par AHMED HUSSEIN , Senior Mechanical Design Engineer , ARKITECHTONICA

1- Chiller Ton = (GPMx∆T (Delta Temp degree fehrenfit)) /24    

2- cooling Tower Ton= ( GPMx∆T (Delta Temp degree fehrenhit)) /30

        

Omer Taha
par Omer Taha , Senior Mechanical Engineer , CEM® I LEED AP® l ASHRAE®CHD , khatib & Alami

Q=m Cv delta t Q=1 ton = 12000 ÷3.41 watt m (mass flow rate ) =v(flow rate) × p(density) Cv= 4200 J/kg.k delta t=5.5 k Q = v×p×Cv×delta t 12000÷3.41= v× 1000 ×4200×5.5 v = 0.00015 m3 / s transfer to gpm = 2.4 gpm

احمد النافع
par احمد النافع , مهندس انتاج , مصنع الشرقاوي

(500)*Q= m * diffT

diffT = 12000/2.4/500

= 10 DEGREE

 

More Questions Like This

Avez-vous besoin d'aide pour créer un CV ayant les mots-clés recherchés par les employeurs?