How do we prevent cavitation in PUMPS?

user-image
Question ajoutée par Yusuf Mohammed , Utility/Maintenance Technician , CCHBC
Date de publication: 2014/09/01
Mohib Shamshad
par Mohib Shamshad , Process Engineer , Energy Enterprise Associates

  1. By controlling fluid temperature.
  2. By checking Available and Required NPSH of pump.
  3. Examine and eliminate any air leakage and seepage.
  4. Increase suction vessel elevation above ground.
  5. Properly size pump piping.

BASSAM MASRI
par BASSAM MASRI , Mechanical Engineer , DAR AL-Handasah Consultants Shair & Partners

Pump cavitation

  1. Vaporization cavitation, To prevent this type of cavitation, the NPSHa in the system must be higher than the NPSHr of the pump.
  2. Internal re-circulation cavitation, you need to open the restricted discharge valve on the pump...
  3. Vane passing syndrome cavitation, To prevent damage due to such cavitation, free space between the impeller blade tips and the cutwater should be at least4% of the impeller diameter.
  4. Air aspiration cavitation, Tighten all joints such as flanges....
  5. Turbulence cavitation.Design the pump suction piping and routig to avoid excess turbulence.

Prevention or Action measures to be taken

Nishant Samarth Nishant Samarth
par Nishant Samarth Nishant Samarth , Manager , RELIANCE INDUSTRIES LIMITED

The dynamic process formation of bubbles inside the liquid, their growth and subsequent collapse is called cavitation. 

The pump always need to have a sufficient amount of suction head present to prevent vaporization at lowest pressure point in the pump. So NPSH is important.

NPSH (Net positive suction head) is the total head at suction flange of the pump less than the vapor pressure converted to fluid column height of the liquid.

Cavitation can be avoided by increasing the NPSHa (Net positive suction head) available greater than the NPSH required.

NPSH available= Pressure head in suction reservoir + Static suction head + velocity Head at pump suction flange - friction head in suction line - vapor pressure of liquid at that temperature.

So as you see in the equation to increase the NPSHa you will have to

  1. Increase the height of the tank
  2. Pressurize the tank
  3. Increase flow of the liquid
  4. Reduce friction by increasing the diameter of the pipe
  5. Reduce temperature of liquid to decrease the vapor pressure

Hisham Anter
par Hisham Anter , مهندس هيدروميكانيكا , بيت الخبرة للاستشارات الهندسية

1-MAKE SURE THAT THE PUMP WORK IN ITS WORKING RANGE

  • 2-  MAKE SURE THAT THE IMPELLER  IS SUBMERGED WITH WATER 

Mayank Sharma
par Mayank Sharma , Project Engineer , Deep Industries Limited

1. NPSH Available should be greater than NPSH Required means available suction head must be greater than required suction head.

2. Proper priming of the pump should be done so that no air is left inside the casing.

3.  Discharge of pump should be uninterrupted to prevent recirculation inside casing.

Roberto Campomanes Abejo
par Roberto Campomanes Abejo , Power Plant Senior Maintenance Manager , Alto Power Management Corporation. International limited

Pump cavitation is the formation of bubbles or cavities in the liquid, developed in areas of relatively low pressure around the eye of an impeller. As the bubbles/cavities travel to the discharge side of the pump, moving to a high pressure area, the cavities implode. The imploding or collapsing of these bubbles triggers intense shockwaves inside the pump, causing damage to the impeller, vibration, and excess noise. 

Srikanta Behera
par Srikanta Behera , Mechanical Lead Engineer , Jereh Oil and Gas Engineering

  1. Internal re-circulation cavitation, you need to open the restricted discharge valve on the pump...

Shaik Anwar
par Shaik Anwar , mechanical supervisor (head) , AL YAMAMA

base should be good bearings  must be in good condition 

Haja Mytheen Mohamed Ali
par Haja Mytheen Mohamed Ali , Maintenance Supervisor , Inshaa Factory

Add corrosion inhibitor- Hydrex 3919 and Hydrex 1565 to your R/O water line with dosing pump.

MD SHAHID  AHMED
par MD SHAHID AHMED , Quality control inspector ( Rotating and Static Equipment) , NBTC

1)You need to open the restricted discharge valve on the pump.

2)The problem could be a clogged downstream filter.

3) A closed discharge valve.

4)An over-pressurized header. Check valve installed backwards Operating the pump at or close to shut-off head.

Richard Padilla
par Richard Padilla , Project Site Engineer , Sraco

1.REDUCING MOTOR SPEED

2.INSTALL AN IMPELLER INDUCER

3.INCORPORATE A BOOSTER PUMP INTO YOUR PUMP SYSTEM

4.REDUCE THE TEMPERATURE OF THE PUMP