We buy chiller for HVAC system for Villa 3 floors every floor 300 meter. approximately how many tons ?

user-image
Question added by Mohamed Deraz , Sales Engineer - HVAC , Class A International
Date Posted: 2014/02/03
Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

55  TONS for complete Villa

just estimated tonnage

 

magdy abd al nour
by magdy abd al nour , HVAC Site manger , First United Co.

form37 ton to60 ton  (you must give me the exact Vila location north Africa or golf or Europe or USA) 

Ehab Tuffaha
by Ehab Tuffaha , MEP Manager , mep enterprises

You need36 to45 ton ; in Gulf we take1 ton for each20 to25 square meter

Babak Kaberi
by Babak Kaberi , Project Coordinator for Engineering Affairs , IOID

first please tell me:

1-where is villa located?

2-is ther any other buildings side to side around it?

 

mohamed sharbudeen ayub
by mohamed sharbudeen ayub , Senior Sales Engineer , Faisal Jassim Trading

Please use heat load calculation software like HAP to get exact results. Load depends upon building structrue, windows, occupancy and orientation. 

Jayakrishnan V G
by Jayakrishnan V G , Project Engineer , Future World Electromechanical LLC

Considering an atmospheric peak temperature of50deg celcius u might require a52 ton machine maximum. But this is just a thumb rule, in my last project the chiller we had selected was having a tonnage of250tons at atmospheric temp of51deg celcius, the same chiller will do380 tons at atmospheric temp of37deg celcius.

sherif abdelhakam fathi rwash
by sherif abdelhakam fathi rwash , مدير مشاريع ميكانيك , المستوي الرفيع

Chiller capacity60 ton at ambiant tempret.46 d. C

 

In USA we use one Ton for every400 squares feet. So after converting300 meters to squares feet I come up with8 Ton for every floor that mean you will need24 ton for your building. If it does not exist in the market go with the next close number like25 Ton or even30 Ton.

 

 

 

300 Square Meters =3229.17312 Square Feet

 

 

 

One Ton for400 Square Feet

 

 

 

3229 ÷400 =8 Ton.

 

 

 

Feel free to contact me with any questions.

 

 

.   

Ismael Hamad
by Ismael Hamad , Trainer , ANTONOIL DMCC , Lukoil project, WQ2

Roughly you need chiller around50-60 ton maximum

Amr Ibrahiem Hussien
by Amr Ibrahiem Hussien , senior HVAC Engineer ( Design - maintenance - construction ) , petromaint

for a rough estimation that take the following consedration :1- highest ambient temp is45 degree celcuis

2-  building is dos't have a wide area of window or glass3- the roof is isolated4- pepole in floor are about10 -15 person

 

you may need a (50 to60 Ton Chiller ) @45 dgree condenser temp ( air cooled )

Mohamed hummieda
by Mohamed hummieda , senior mechanical engineer , italconsult

The l Heat load calculation is depend on many factors as1_ city2_ direction of building estemate heat load gain from solar through walls and through roof if exposed for outdoor or not Generaly its need to conduct heat load calculation using programs as hap or elite so can determine the load estemation then can indicate capacity of chiller required Approximatly if in ksa need to about1 ton per20_25 sq meter total about45 ton will be e