Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

When a single equipment grounding conductor is run with multiple branch circuits in the same raceway or cable, how shall it be sized?

user-image
Question added by Mohamed salman faris , QC QA Electrical Engineer , King Abdullah University Of Science And Technology
Date Posted: 2013/05/19
munther khatib
by munther khatib , Senior project manager , Alfanar Construction Company

This will be according to the short circuit calculation.
The maximum allowable current and the duration of fault will be considered.
However, the allowable duration is usually one second.
Actually, in low voltage system, the practice is not to lay a separate cable or wire for grounding.
Instead, the shielded copper of the low voltage cable will be heat-shrinked, lug-pressed and earth the equipment.

Waseem Shamieh
by Waseem Shamieh , Head Of Electrical Department , Abdoun For real Estate

It shall be sized for the largest overcurrent device protecting conductors in the raceway or cable.

Mohamed Shehata Mohamed
by Mohamed Shehata Mohamed , Electrical Engineer (Reserve Officer) , armed forces, air defense department

this will be according to the short circuit calculation.
The maximum allowable current and the duration of fault will be considered.

mohammed yusuf
by mohammed yusuf , فنى كهرباء عام , اركان للصناعه والتعدين

this will be according to the short circuit calculation.
The maximum allowable current and the duration of fault will be considered

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.