Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

علم التكييف ؟ ما هو افضل ترتيب للزيادات التي تضاف على خط chilled water

خط الماء الخارج من الشلز والداخل على الشلر ما هي الاشياء الهامه التي يجب ان تضاف الى الخط وكيف يكون ترتيبها ؟؟

user-image
Question added by thaer tanenah , Sr. MEP Quantity Surveyor , AL Arrab Contracting Company ACC
Date Posted: 2013/05/06
Yasser ELkhateeb
by Yasser ELkhateeb , CEM & Industrial Utilities & Energy Manager , Pirelli Egypt

Sure for both Inlet and Outlet Line: Gate Valves, Pressure guages

But the most important is stariner for Inlet line with mish number less than25micro

to protect heat exchanger for both cooler and condenser

other elements should be measured by Chillers

 

Supply lineGate valve / strainer / gate valve / stopcock Peter Fly / counter pressure / thermometer / Flow SwitchReturn lineBalancing valve / counter pressure / thermometer

Ahmad Imran
by Ahmad Imran , Senior Mechanical Engineer , Saudi Arabian Baytur

inlet : GV , Strainer , PG , T , union

outlet : union , PG , BV, (Bypass with GV after BV) , GV

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.