Can i use fresh air concept in fcu?

user-image
Question added by Abdulla shaik , Mechanical Engineer , LC lusail Consultants
Date Posted: 2016/03/18
Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

yes can be done but it has to be noted that it may not achieve the humidification or dehumidification since there are some limitations for the FCU.

chetan sharma
by chetan sharma , Senior project engineer , trinity engineering services

yes it can be employed usually we employ this system in case of small villa since the cost of fahu would be too high .keep in mind to consider the unit with the percentage of fresh air used remember to feed with fresh air fcu in corridor area 

farooqui mohammad
by farooqui mohammad , Estimator , Kharafi National

Yes It should be used for a healthy indoor air quality

harish alam
by harish alam , Mechanical Engineer , Seder Group

Yes, Definitely you can add fresh air to the FCU.

At our project we have added fresh air coming from the fresh air handler unit(FAHU) to the return plenum of FCU.

Mohammed Hamdy
by Mohammed Hamdy , MEP Planning Engineer , ASAS-Electromechanical CO,

In most cases fresh air is delivered to the rear of the fan coil unit, Which mixes this air with the re-circulated air from the space and delivers it to the room, the benefit being that that the fresh air is conditioned before it is delivered

Khurshid Siddiqui
by Khurshid Siddiqui , Lead HVAC Engineer , Wood Group

You can use Fresh Air in FCU, provided that FCU coil selection is done considering load of Fresh Air. But FA must be connected with RA Plenum or near RA inlet otherwise there will be humidity inside the False Ceiling that will cause Fungus.