How to take pressure drop for Return air gap?

user-image
Question added by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL
Date Posted: 2016/03/06
Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

The pressure drop is negligible but what can be done is to compare the size of return air gap with any grille of same size and same CFM and check the noise level and pressure drop across.

Sherif Mohammed Ibrahim
by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

Basically we consider it as a free return so there is no pressure drop and if there any it will be negligible.

Moustafa Mohamed Galal Saber
by Moustafa Mohamed Galal Saber , Mechanical Engineer , BEEAT ALMEMAR ENGINEERING CONSULTANTS & PARTNERS

The pressure drop in Air return gap or ( Air plenum ) is taken as 0.05 in wc (12.5 Pa ) which is a negligible  value as compared to the conventional  Return air duct pressure drop.  

chetan sharma
by chetan sharma , Senior project engineer , trinity engineering services

10 to 15 pa is believed to be ideal pressure drop form return air gap usually the air gap is neglected as it is free return so no need to consider 