How to Connect driver to three phase motor in Case of Phase loss? and how much will be the load?

I have three phase motor and one phase lost so i want to connect the Driver to overcome this Problem .

if I use a capacitor to start up the motor I will loss percent of the Motor .

I want the answer with Details about how to calculate the load .

user-image
Question added by mustafa محمد صادق السيد , Electrical Engineer , rmc
Date Posted: 2016/03/04
Senad Sakic
by Senad Sakic , Planer , cts GmbH

It is not recommended that three phase motor works on two phase, all modern softstarter or frequency drive has this protection integrated in its so it is not possible that motor works on two phase.

If can't use electronic starter than you can use relay for phase monitor which will shut down motor in case of phase loss.

Hasan Zainy
by Hasan Zainy , Control / Instrumentation Filed Service Engineer , GE

i have no expertize in this.

 

looking with you for the answer

Well, In industry , if a phase is lost YOU SHOULD repair it. There is NO other solution with only tow phases.

For small motors, a capacitor can be used to function with tow phases, but the torque won't be the same as functionning with 3 phases.

Thabet Almezwk
by Thabet Almezwk , QC/QA Engineer , Alfanar Electrical system

thanks

sure for 3 phases motor and in critical situation you can convert it to be as single phase but note here that power will be less

the way is by connection one capacitor between 2 phases

the value of it depend on voltage, if 220V so for each horse power you need50 micro farad capacitor

please refer to below link for more clear

 http://www.electrobrahim.com/2014/12/demarrage-un-moteur-triphase-en-monophase.html

muhammad iqbal
by muhammad iqbal , Electrical Engineer , M C DEAN INC< USA

Dear Mustafa. Your question is kind of confusing. If it is a three phase motor and you have lost one phase, it is not going to run. The protection is going to take it out of service until the time you get the third phase restored. In the event of one phase gone, you will be left with two third or 67% of load as you will have an open delta situation.I do not understand the Capacitor part which generally is used to improve power factor efficiency.