What are the maximum air speed at the supply diffuser?

user-image
Question added by aly ahmed , site engineer , SMG
Date Posted: 2015/06/22
magdy abd al nour
by magdy abd al nour , HVAC Site manger , First United Co.

700 fpm for residintial

1000 fpm for the public

 

1400 fpm for industrial

Hasan Riaz
by Hasan Riaz , Mechanical Engineer , Saudi Bin Ladin Group (Hamad International Airport)

Above velocities are I think at the main duct. At the supply diffuser, the velocity should be400 -500 FPM for low velocity Air Conditioning Applications.

ROBERT CALIMLIM
by ROBERT CALIMLIM , QA/QC Manager -HVAC Design Engineer , Shimizu /DCJC

I agreed mr.riaz with 400-500 fpm (2.0-2.5)m/s , It was called terminal velocity. In selection of diffusers plz check the NC level , the lower NC more better (30NC)  .

 

neck size:

1. 150mm X 150mm - 50lps (105cfm) --- 6"X 6"

2. 225mm X 225mm- 100 lps( 211 cfm)--9" X 9"

3. 300 mm X 300mm -381 lps(381 cfm)--12"X12" ----maintain up to this diffusers , 300 cfm above can create noise above 30NC.

 

Thanks

Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

It depends on noise and throw but normally it is 2.5 - 3.5 m/s

Sherif Mohammed Ibrahim
by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

the speed is to FPM to insure a quiet sound level

chetan sharma
by chetan sharma , Senior project engineer , trinity engineering services

the maximum flow rate and velocity depends in the type of usage generally it ranges from 2.4 mtr/sec to 3.4 mtr /sec in ideal condition in case of special industrial application refer to ashrae standard and DW 144/143 and SMACNA standards