What will be megar resistance value for LV cable like pvc xlpe and others that we can confidently say that is good cable

user-image
Question added by nadeem ahmad rajput , Electrical Supervisor , Mash Hospital multan
Date Posted: 2015/04/09
Leonardo Banzali
by Leonardo Banzali , Electrical Maintenance-trainer , Sadara Chemical Company

Depending on voltage rating & applied test voltages, most common LV cables rated up to  600V when applied with  1000V DC test voltage should give an acceptable result of  100 Mega Ohms or higher.

Safi Ullah
by Safi Ullah , Electrical Trainee Engineer , PESCO (Peshawar Electric Supply Company)

A good cable means good conductor, so a good cable will have comparatively low resistance and high conductivity.

Zirak Salik
by Zirak Salik , SR. ENGINEER- ELECTRICAL , REDCO CONSTRUCTION- ALMANA

For LV XLPE cables, the acceptable readings should be as follows to justify if the cable is good;

1. Insulation Resistance Test ≥1.0 MΩ2. Continuity Test ≤1.0 Ω

Dinesh Sooriyaarachchi
by Dinesh Sooriyaarachchi , MEP Engineer. , Linc Facility Services

Usually use250V also. The result should be over500 Mh. But if can use1000 V, it is much better and result over100 Mh. is preferable.

Sudhakar Nandigamu PMP
by Sudhakar Nandigamu PMP , Project Manager/Sr.Electrical Engineer , MTC Qatar

Agree with Leonardo Banzali 

gaber oraby
by gaber oraby , Site Project Manager , ACCURATE (MEP PROJECTS)

according to applying voltage 