What is the testing pressure for chilled water pipes?

user-image
Question added by Ahmad Imran , Senior Mechanical Engineer , Saudi Arabian Baytur
Date Posted: 2013/07/31
Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

1.5 to2 times working pressure or12 bar  

Prabhakar Naik
by Prabhakar Naik , Engineering Manager , VASTU & ENGG CONSULTANCY DMCC, JLT

1.5 times the working pressure or10 bar whichever is higher.

ismail shaikh
by ismail shaikh , hvac technician , dubai health authority

testing pressure is8 bar

Siby Blesson
by Siby Blesson , Estimation Engineer , Resi air

Usually when testing, we put the Chilled water pipe, Shedule40 MS pipes at12 bar minimum to know whether ther is any leak from elbows, joints, flanges, flexible connectors. After running, it can be given at8 Bar.