ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

After calibrating a transmitter we fixed it in a process line. At live zero condition the Tx shows 4.5 mA. what should we do to make the Tx show 4 mA?

user-image
تم إضافة السؤال من قبل Mahmoud Mohammed , Technical Manager , Optimum Engineering and Trading Company
تاريخ النشر: 2013/12/04
Mahmoud Mohammed
من قبل Mahmoud Mohammed , Technical Manager , Optimum Engineering and Trading Company

Isolate the Tx from process and fully depressurized it and checked if it reads4 Ma then calibration is OK and carried out flushing of both impulse lines and gain take it in service it should read zero or4 Ma. 

Ahmed Hamdy Ahmed
من قبل Ahmed Hamdy Ahmed , Senior Instrumentation And Control Engineer , Middle East For Oil Refinery

Firstly isolate the tap points and release the pressure  then check the zero value after isolation if shifted calibrate Zero Then calibrate span.

Ankit Thummar
من قبل Ankit Thummar , Instrumentation Engineer , Staple Fiber Division, Grasim Industries Ltd.

Just perform a zero trim action online, and it will be set as zero.

المزيد من الأسئلة المماثلة

هل تحتاج لمساعدة في كتابة سيرة ذاتية تحتوي على الكلمات الدلالية التي يبحث عنها أصحاب العمل؟