ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

How to calculate cfm to tr?

user-image
تم إضافة السؤال من قبل sachin bait
تاريخ النشر: 2016/03/01
Muhammad Arsalan Siddiqui
من قبل Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

Cooling BTU’s = 4.5 X CFM X Change in enthalpy

you can get enthalpy change from initial and final condition of air by psychometric chart.

Normally DX system gives 400 CFM / Ton but under certain conditions mentioned in their catalouge.

 

Syed Izhar  Mustafa
من قبل Syed Izhar Mustafa , Mechanical Engineer , Attiq ur Rehman Contracting Company

Thumb-rule 400 cfm per ton of cooling is needed for normal comfort applications, 500 cfm per ton of cooling for heat pump and high sensible heat applications, and 350 cfm per ton of cooling for high latent heat applications.

Serge Lalonde
من قبل Serge Lalonde , Fire Prevention, Inspection, Repair , Sprouse Fire Health & Safety

1TR = 400 CFM Delta T in F X Flow in USGPM / 24 

Sherif Mohammed Ibrahim
من قبل Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

the next formula has been taken from carrier catalog it may change from brand to other

Tidb = inlet dry bulb F

Tedb = exit dry bulb F

as a rule of thumb

for circulating supply and return units 300 :400 cfm per ton

For total fresh air units 150: 200 cfm per ton

santosh kumar
من قبل santosh kumar , BIM ENGINEER (MEP) , SANRACHNA

1 TR= 400 CFMEX. 10000CFM/400= 25 TR 

المزيد من الأسئلة المماثلة

هل تحتاج لمساعدة في كتابة سيرة ذاتية تحتوي على الكلمات الدلالية التي يبحث عنها أصحاب العمل؟