How to calibrate the pneumatic instruments?

user-image
تم إضافة السؤال من قبل vinoth loganathan , Inspection Engineer , Venture lighting pvt.ltd
تاريخ النشر: 2015/12/23
Ayoob Ahamed
من قبل Ayoob Ahamed , Calibration Engineer , Saudi Arabian Sensing Solutions Company Limited (SASSCO)

HI Vinoth, there are many types of pneumatic instruments. Please be specific which one you want to know about so that you will get a better answer. Generally calibration requires a sourcing instrument, a standard reference instrument and the test meter.

Yehia Adlouni
من قبل Yehia Adlouni , Engineering Maintenance Manager , Birchwood Foods

For Pressure Gage: You can calibrate it with standard calibrated Gage with the same range by using oil pressure tester or air pressure tester on the different ranges (0%,%,%,% &% of the range).

For pressure transmitters & Pressure switches you can calibrated too with standard calibrated Gage with the same range by using oil pressure tester or air pressure tester on the different ranges (0%,%,%,% &% of the range).

Chinmay Ray
من قبل Chinmay Ray , Engineer , Lanco Group

Calibration is one of the primary process used to maintain instrument accuracy.

To calibrate an instrument involves checking that the out put of the given instrument corresponds to given inputs at several points throughout the calibration range of instruments , although the exact procedure may varry from product to product.

 

abdelkader chelli
من قبل abdelkader chelli , chef de section instrumentation depuis novembre1988 , sonatrach algerie et fertial algerie ex asmidalalgerie

calibrer un instrument de mesuredisposer de l'energie pneumatique , electrique ou hydrauliqueconnecter l'instrument à l'energie d'alimentation et de commadeappliquer dans la chambre de mesure une force de signal equivalente  à 0% de l'echelle  de mesure et regler  le signal de sortie  à la valeur minimale  de l'echelleune force de signal  équivalente à100% de l'echelle de mesure  et regler le signal de sortie à sa valeur maximum de l'echelleune force de signal intermediaire  equivalente à 25% et 50%   pour parfaire la linéarité et regler le signal de sortie correspondant à 25% et 50%200mbar .....1000mbar pour le pneumatique echelle de sortie

alimentation  pneumatique  1400mbar generalement OU 20 PSI

Muhammad Shaheer Thalikassery
من قبل Muhammad Shaheer Thalikassery , Maintenance Engineer - Instrumentation , Air Liquide Arabia

For pneumatic instruments you should have a pressure source (Gas cylinder or pressure pump), with either oil or gas, make sure not using oil for oxygen service instruments.

devide the range and apply pressure atleast five divisions ascending and descending ways. (both should be done to check hysterisis).

record the output and calculate error :)

mario mayol
من قبل mario mayol , Instrument Coordinator , Daelim Saudi Arabia

Seals offer another advantage over wet legsthere is more versatility for mounting the transmitter. The transmitter can be located above the tap. This is particularly helpful when the tank is buried or if the transmitter must be located in a more convenient area. The transmitter can be mounted above the tap as long as the back pressure on the seal does not exceed 1 atmosphere of pressure (33.9 feet). When the seal is above the tap, the level calculation is slightly different because the distance must be subtracted from the level instead of added.

Mohamed Uvais Jainudeen
من قبل Mohamed Uvais Jainudeen , I&C Engineer , Saudi Consulting Services (Saudconsult)

Dear Vinoth, 

There are many pneumatic instruments which are used in measurement and control purpose. All instruments are calibrated in different procedures but principles are same. Calibration of instrument is a form of verification of instrument by using high accuracy instruments (Master Instruments). Please specify instrument you want to calibrate to explain in deep.

Yefatima Koroma
من قبل Yefatima Koroma , Surgical nurse , Estern Community Goverment hopital

Hart Communicator 2500hms. 20.000 loop calibrator. digital pressure calibrator. It is apordable pressure means.

Merzouk Belhamel
من قبل Merzouk Belhamel , Instrumentation Foreman Principal Level 2 , sonatrach Hassi R'mel

Pour calibrer un instrument pneumatique exemple Transmetteur pneumatique: 1 savoir entendue de l’échelle du transmetteur selon le document du procédé exemple 0-6000mmH2O. Premaration des appareils nécessaires comme Alimentation du transmetteur 1.4bar ; instrument de mesure de la sortie du transmetteur qui est 0.2b - 1bar. c'est a dire 0 mmH2O donne 0.2 Bar et  6000mmH2O donne 1bar puis on vérifie 300mmH2O donne 0.6 bar et pour une bonne linéarité on verifie 25% =0.4b et 75% =0.8.  

Vijayakumar Ramalingam
من قبل Vijayakumar Ramalingam , Electrical & Industrial Automation Engineer , Masafi Co.LLC

This is control valve calibration not transmitter, for control vale calibration we have to used pneumatic source from this source we can give pressure from 3psi to 15 psi.